RECTANGULAR FIRE DAMPERS FD-EI240S
The rectangular fire dampers provide protection against a possible fire spreading through ventilation – air conditioning ductwork, for 240 minutes.
The fire dampers are used in ventilation and air conditioning installations serving office buildings, industrial buildings, commercial areas, hospitals, concerts and competition halls.
The fire dampers close automatically at the occurrence of high temperatures by means of a spring or anactuator.
Our company produces rectangular fire dampers in order to isolate the gaps between the fire compartments.
- Tested according to the EN 1366-2: 2015 standard
- Any direction of air flow
- CE certificate according to EN 15650: 2010
- Protection against corrosion according to EN 15650: 2012
- Air losses in accordance with EN 1751, Class 2
- Declaration of Performance according to Regulation (EU) No. 305/2011
- Certificate of Conformity issued by the manufacturer
CONSTRUCTION DESCRIPTION
The fire damper is made of: casing, locking element (blade) and a device for trigger and control, operated remotely or automatically after the thermal shutter is operated.
The casing is made of fire-resistant material, of (MGO) magnesium oxide type, with 20 mm thickness.
Inside the casing there are the expansion gasket, the shutter blade, elements ofthe actuating mechanism, the sealing profile (for ensuring tightness at ambient temperature) and the fire expandable sealing (Intumex L-HP) in order to ensuretightness in case of fire.
The locking element is made of Fireboard (MGO) sandwich panels with a thickness of at least 60 mm (20 mm MGO + 20mm mineral wool + 20 mm MGO).
This thickness ensures fire resistance for 240 minutes.
The actuating mounting (consisting of motor and support) is mounted on the outside of the casing.
The fire dampers are equipped with Belimo/Siemens type actuator, mounted on the shaft of thelocking valve. When the actuator is supplied with voltage, it rotates by bringing the damper to the closed position (operating position), while tensioning the return spring.
The fire dampers with Belimo/Siemens type actuators close by interrupting the power supply, with the result ofdriving the return spring located in the actuator.
Triggering and control mechanisms: Belimo/Siemens type axial actuator, from the series of products intended for fire dampers.
The correct functioning of the fire dampers is ensured when the axis of rotation is the horizontal one.
In order to be ensured the fire resistance of the separation element, there shall be observed therestraint limits – the rotation axis of the fire damper will not go beyond the wall.
Followinga proper installation of the fire damper, in case it has controls or other elements that require connection to the electrical system, the cables of this system must be properly connected to the fire damper.
1. metal flange
2. casing made of fire-resistant material
3. fire damper door
4. motor/spring actuating mechanism
5. cold sealing gasket
6. intumex tape
7. door stopper
8. open/closed driving mechanism
INTERIOR AND EXTERIOR SIZE
The interior size is the size of the damper casing on the inside.For example, a FD – EI240S 4NM – T 800×500 fire damper has the horizontal interior size (x) 800 mm and height (Y) of 500 mm. Usual sizes:
Upon the beneficiary’s request, the FD-EI240S dampers can be madein other sizes than those in the table.
In order to know the overall dimension of the fire damper, it is calculated the interior size + 70 mm, representing the flange of attachment in the wall. To this dimension it must also be taken into account that on the side with actuator it is added another 60 mm over the outer dimension.
The depth of the 240-minute fire dampers varies depending on the Y size of the damper. In the case of the FD – EI240S 4NM – T 800x500fire damper, the depth is of 400 mm, without the attachment flange. This depth varies as follows:
- 200 ≤ Y ≤ 250, debth = 250 (without the attachment flange);
- 250 < Y ≤ 300, debth = 300 (without the attachment flange);
- Y > 300, debth = 400(without the attachment flange).
TECHNICAL SPECIFICATIONS
DECLARATION OF PERFORMANCE
The unic code of the product | FD-EI240S |
---|---|
Purpose | The fire dampers are used in ventilation and air conditioning installations and provide protection against a possible fire spreading through the ventilation and air conditioning ductwork, for 240 minutes. |
Manufacturer | SBI Steel Industry SRL, Aurel Vlaicu street, no.13, Ilfov, Romania |
Declaration of performance according to EN 15650: 2010 standard | Fire resistance according to EN1366-2 standard and classifications according to EN 13501-3 standard. |
ESSENTIAL FEATURES | PERFORMANCE | TECHNICAL SPECIFICATION |
---|---|---|
Response time • when closing |
COMPLIANT | În timpul testului clapeta rezistentă la foc s-a închis în 2 min. conform EN 1366-2 |
Operational fiability • Closing and opening cycles, 50 cycles |
COMPLIANT | There have been carried out 50 tests of closing and opening before the fire test (EN15650 cl. 4.3.1. a) |
Fire resistance | ||
• Fire tightness (E) | COMPLIANT | E according to SR EN 15650 |
• Insulation (I) | COMPLIANT | EI according to SR EN 15650 |
• Leakage flow (S) | COMPLIANT | ES according to SR EN 15650 EIS according to SR EN 15650 |
Durability of the response delay • The response of the temperature-sensitive element and the bearing capacity |
COMPLIANT | The thermal triggering mechanism responds to high temperatures and the load capacity of the sensor is in accordance with EN 15650 cl.5.2.5. |
SYMBOLS
Where the significance of the codes is:
- FD – rectangular section fire damper
- E – fire tightness
- I – air tightness
- 240 – time that is ensured up to 240 minutes.
- S – smoke tightness
- Ve – the fire damper is closingvertically
- Ho – the fire damper is closinghorizontally
- I <-> o – sense of protection insurance: interior -> exterior and exterior <- interior
- B – width of the fire damper (mm)
- H – height of the fire damper (mm)
CERTIFICATION
Fire resistance according to EN 1366-2
Tightness class 2 according to EN 1751 standard
CE marking
CODING
Example
– with fuse and trip start/end contacts: FD – EI240S – F -2C – 600×400
– 24V motorization with thermal sensor:FD – EI240S – 4NM – T – 600×400
THE WAY OF ACTUATING THE FIRE DAMPER
Our services provide two actuating ways for closing and opening the fire resistant damper. These are: fuse with return spring and actuator with return spring and optionally equipped with thermal sensor.
In the case of driving the fire damper door by an actuator, its type is chosen depending on its power and the size of the fire damper. The fire-resistant dampersare equipped with Swiss actuators, made by Belimo or German motors, made by Siemens.
After choosing the motor power, it will be opted for the operating voltage. This can be 220 or 24 volts. Optionally you can choose to equip the fire damper with a thermal sensor, which will trigger the actuator at the set temperature of 72.
DELIVERY AND ACCOMPANYING DOCUMENTS
DELIVERY
The fire dampersdelivery will only take place accompanied by the following documents:
– Document of origin
– Declaration concerning quality and conformity
– Declaration of performance
– Directions for installation
– Maintenance and operating directions
On the fire damper it is attached the product label specifying the product identification data (sizes, batch series, manufacturing date), as well as the CE marking number.
The beneficiary has to check the compliance of these data with those of the ordered product.
POST-DELIVERY WARRANTY
The warranty period of the product is 24 months from the date of signing without objection the document of origin (delivery note and/or invoice), but not more than 65 months from the delivery, subject to putting into operation according to the technical documentation and compliance with the conditions of transport, handling, storage and mounting according to the directions.
- Handling of the product will be done manually, while complying with the labor protection norms regarding the weight and the protection equipment required for handling.
- The transport will be carried out in such a manner that during the loading/unloading and travelling it is not allowed to strike, bend or destroy the product.
- The product storagewill be made in specially arranged places until the date of mounting. The storage area will be protected from the action of atmospheric agents.
- The mounting, operation and periodic verifications of the product/spare part will only be executed by qualified or authorized personnel.
- During the warranty period, there will be borne all costs incurred with fixing the product broken-down due to hidden material defects or manufacturing defects that can be proven.
- Notification of the manufacturer by the beneficiary concerning the defect of the product within the guarantee time limit will be in writing (letter or fax) or by e-mail with the highlighting of the defect type as detailed as possible.
- There can be also provided guarantee against a fee for the repaired products or spare parts which are outside the warranty period.
Special mentions:
The guarantee right will be lost if the beneficiary:
- Damages the product during transport or due to improper handling;
- Damages the product due to thermal, mechanical or plastic actions caused by fire, mechanical tensions, weathering or mounting not in compliance with the manufacturer’s instructions or the norms and laws in force, applicable in the field of construction;
- Operates the product in humid, corrosive environments, excess dust, limit temperatures, other than those for which it was designed;
- The product is operated by other persons, other than the trained/qualified or authorized personnel;
- The beneficiary is advised that, for the proper functioning of the product, to ensure the execution of regular maintenance operations, respectively checking the integrity and functionality of the components.
STORAGE AND TRANSPORT
TRANSPORT
For transport the fire dampers will be individually packed or grouped on a wooden pallet and wrapped. In the truck it will be ensured a protection against shocks. It is not advisable to transport in uncovered cars if the weather is unfavorable.
It should be taken into account that the temperature inside the car must not exceed 65 ᵒC.
During transport the fire damper door will be in the closed position.
Check the fire dampers at the goods arrival to see if there is any damage. In case of finding any damage or lack, please contact immediately the shipping company and the supplier.
STORAGE
For storage there are no required special conditions, but it is recommended a dry place and away from direct sunlight. The storage temperature cannot degrade the fire dampers, but it should be taken into account not to exceed 65 degrees C. At 72 degrees C the thermal sensor is triggered, if this happens, it will be necessary to replace it.
MOUNTING ISTRUCTIONS
MOUNTING
Before starting the mounting proper, please read these directions for installation.
The mounting should be carried out by qualified personnel, such as electricians, HVAC technicians, or persons with technical knowledge.
The fire dampers are mounted on ventilation ducts, at the wall bushings through the walls defining the fire compartments.
The opening fill will be carried with basaltic mineral wool (having a density between 140 -180 kg/m3 – e.g. 50 mm ROCKWOOL mineral wool) and the outer sides will be finished with common finishing items (drywall, plaster putty – e.g. Rigips).
Phase 1. Hole in the wall is made with sizes of 100 mm larger than the size of the FD-EI 240S fire damper.
Phase 2. Place a layer of mineral wool (density between 120-140 kg/m3 – e.g. ROCKWOOL mineral wool) of 50 mm thickness. Above it put the FD-EI240S fire damper.
Phase 3. The mounting of the FD-EI240S fire damper inside a construction element should be made so as,when closed, the blade to be in front of it.
Phase 4. Fill the remaining gap with basaltic mineral wool.
Phase 5. For finishing, cover the area between the wall and fire damper with strips of cardboard gypsum of minimum 150 mm width. For cold sealing, apply silicone to the joint area between the cardboard gypsum and the fire damper.
Phase 6. Following the installation, check that fire damper is functioning properly.
MAINTENANCE
In order to ensure the correct and uninterrupted operation, the FD-EI240S type fire dampers must be inspected and operated regularly.
Rectangular fire dampers require an execution of service verifications every six months.
Each verification of the rectangular fire dampers shall be completed with an adequate report.
Controls recommended for fire dampers
Operation / task | Result |
---|---|
Fire damper reference | |
Control date | |
Checking the damages related to the wiring of the actuating mechanism (if appropriate) | |
Checking for damages related to the end switch wiring (if applicable) | |
Checking the fire damper cleanliness and cleaning if necessary. | |
Checking the condition of the blades and seals, correcting and recording if necessary. | |
Confirming the functioning of the safety closing of the fire damper according to the manufacturer’s instructions. | |
Confirming the opening and closing of the fire damper with the help of the control system and by visual observation of the fire damper, correcting and recording if necessary. | |
Confirming the opening and closing of the end switches, correcting and recording(if applicable). | |
Confirming whether the fire damper fulfills its role within the control system (if applicable). | |
Confirming if the fire damper is in the normal operating position |
Rectangular fire dampers are an integral part of an installation. It is recommended to check the system entirety according to the requirements related to the installation operating and maintenance.
The lifetime of rectangular FD EI240S fire dampers is 25 years.